KA Series Chain drives (Twin)
KA 66-TW
-
Can be used for openings for smoke exhaust; D+H Euro SHEV in accordance with EN 12101‑2; and for daily ventilation
-
With BSY+ motor and synchronised electronics controlled via microprocessor
-
High‑speed function (HS) for especially fast opening windows in case of fire (SHEV)
-
2 drive chains for optimal power application to the sash
-
Special chain stabilisation
-
Relief of pressure on window gasket after closing process
-
Electronic force and position control
-
Programmable drive functions and different drive parameters
-
Running speed in CLOSED direction decreases to 5 mm/s (passive closing edge protection)
-
Time-controlled reversing when an obstacle is detected in the CLOSED direction (active closing edge protection)
Approvals / Certificates
Designs and technical data
KA-TW-BSY+ | KA 66-TW | KA 66/600-TW1 | KA 66/800-TW1 | |
---|---|---|---|---|
Supply | 24 V DC / ±15 % / 2 A | 24 V DC / ±15 % / 2 A | 24 V DC / ±15 % / 2 A | |
Duty cycle | Variable designs possible | 30 % (ON: 3 min. / OFF: 7 min.) | 30 % (ON: 3 min. / OFF: 7 min.) | 30 % (ON: 3 min. / OFF: 7 min.) |
Force of pressure | 600 N | 600 N | 600 N | |
Tensile force | 600 N | 600 N | 600 N | |
Nominal locking force ** | 3000 N | 3000 N | 3000 N | |
Service life | 20000 double strokes * | 20000 double strokes * | 20000 double strokes * | |
Stroke | - | 600 mm | 800 mm | |
OPEN running speed | 11.8 mm/s | 11.8 mm/s | 11.8 mm/s | |
OPEN running speed - SHEV | 12.2 mm/s | 12.2 mm/s | 12.2 mm/s | |
CLOSED running speed | 11.8 mm/s | 11.8 mm/s | 11.8 mm/s | |
Show more information
|
||||
Request & Compare |
KA-TW-BSY+ |
KA 66-TW
|
KA 66/600-TW1
|
KA 66/800-TW1
|
Configure now |
* For vertical use, please consult with D+H Sales!
** Depending on the mounting, *** in accordance with VdS 2580