CDM Series Chain drives
CDM-5-ACB
-
Can be used for openings for smoke ventilation; D+H Euro SHEV in accordance with EN 12101‑2; and for daily natural ventilation
-
With BSY+ motor and synchronised electronics controlled via microprocessor
-
Option of up to 4 drives in one synchronous group
-
High‑speed function (HS) for especially fast opening windows in case of fire (SHEV)
-
Low running noises thanks to the innovative acoustic decoupling of the drive components
-
Direct control via 230 V AC
-
Special chain stabilisation and centred chain outlet
-
Compact design thanks to triple deflection of the chain
-
Use of a highly efficient, wear-free brushless motor
-
Relief of pressure on window gasket after closing process
-
Programmable drive functions and different drive parameters
-
Integrated ACB (Advanced Communication Bus) bus interface with Modbus RTU protocol
-
The drive is integrated directly via open bus communication through the ACB (Advanced Communication Bus), e.g. in a building management system
Designs and technical data
CDM-5-ACB | CDM-5-ACB | CDM-1000-0600-5-ACB M1 | CDM-1000-0600-5-ACB M2 | CDM-1000-0600-5-ACB S1 | CDM-1000-0800-5-ACB M1 | CDM-1000-0800-5-ACB M2 | CDM-1000-0800-5-ACB S1 | CDM-1000-1000-5-ACB M1 | CDM-1000-1000-5-ACB M2 | CDM-1000-1000-5-ACB S1 | |
---|---|---|---|---|---|---|---|---|---|---|---|
Supply | 120 ... 230 V AC / +10 % ... -10 % / 50 ... 60 Hz | 120 ... 230 V AC / +10 % ... -10 % / 50 ... 60 Hz | 120 ... 230 V AC / +10 % ... -10 % / 50 ... 60 Hz | 120 ... 230 V AC / +10 % ... -10 % / 50 ... 60 Hz | 120 ... 230 V AC / +10 % ... -10 % / 50 ... 60 Hz | 120 ... 230 V AC / +10 % ... -10 % / 50 ... 60 Hz | 120 ... 230 V AC / +10 % ... -10 % / 50 ... 60 Hz | 120 ... 230 V AC / +10 % ... -10 % / 50 ... 60 Hz | 120 ... 230 V AC / +10 % ... -10 % / 50 ... 60 Hz | 120 ... 230 V AC / +10 % ... -10 % / 50 ... 60 Hz | |
Performance | Variable designs possible | 80 W / 85 VA | 80 W / 85 VA | 80 W / 85 VA | 80 W / 85 VA | 80 W / 85 VA | 80 W / 85 VA | 80 W / 85 VA | 80 W / 85 VA | 80 W / 85 VA | 80 W / 85 VA |
Duty cycle | 30 % (ON: 3 min. / OFF: 7 min.) | 30 % (ON: 3 min. / OFF: 7 min.) | 30 % (ON: 3 min. / OFF: 7 min.) | 30 % (ON: 3 min. / OFF: 7 min.) | 30 % (ON: 3 min. / OFF: 7 min.) | 30 % (ON: 3 min. / OFF: 7 min.) | 30 % (ON: 3 min. / OFF: 7 min.) | 30 % (ON: 3 min. / OFF: 7 min.) | 30 % (ON: 3 min. / OFF: 7 min.) | 30 % (ON: 3 min. / OFF: 7 min.) | |
Force of pressure | 1000 N | 1000 N | 1000 N | 1000 N | 1000 N | 1000 N | 1000 N | 1000 N | 1000 N | 1000 N | |
Tensile force | 1000 N | 1000 N | 1000 N | 1000 N | 1000 N | 1000 N | 1000 N | 1000 N | 1000 N | 1000 N | |
Nominal locking force | 3500 N | 3500 N | 3500 N | 3500 N | 3500 N | 3500 N | 3500 N | 3500 N | 3500 N | 3500 N | |
Service life | > 20000 double strokes | > 20000 double strokes | > 20000 double strokes | > 20000 double strokes | > 20000 double strokes | > 20000 double strokes | > 20000 double strokes | > 20000 double strokes | > 20000 double strokes | > 20000 double strokes | |
Stroke | - | 600 mm | 600 mm | 600 mm | 800 mm | 800 mm | 800 mm | 1000 mm | 1000 mm | 1000 mm | |
OPEN running speed | 7 mm/s | 7 mm/s | 7 mm/s | 7 mm/s | 7 mm/s | 7 mm/s | 7 mm/s | 7 mm/s | 7 mm/s | 7 mm/s | |
OPEN running speed - SHEV | Configuration dependent | 11.5 mm/s | 11.5 mm/s | 11.5 mm/s | 15 mm/s | 15 mm/s | 15 mm/s | 18.5 mm/s | 18.5 mm/s | 18.5 mm/s | |
Show more information
|
|||||||||||
Request & Compare |
CDM-5-ACB |
CDM-5-ACB
|
CDM-1000-0600-5-ACB M1
|
CDM-1000-0600-5-ACB M2
|
CDM-1000-0600-5-ACB S1
|
CDM-1000-0800-5-ACB M1
|
CDM-1000-0800-5-ACB M2
|
CDM-1000-0800-5-ACB S1
|
CDM-1000-1000-5-ACB M1
|
CDM-1000-1000-5-ACB M2
|
CDM-1000-1000-5-ACB S1
|
Configure now |
The matching bracket for CDM-5-ACB
Please note: To install the drives, you will need 1x frame bracket and 1x sash bracket. Additional washers and fastening materials may be required for these brackets. Please contact your D+H partner for this.