CDM Series Chain drives
CDM-1-ACB
-
Can be used for openings for smoke ventilation; D+H Euro SHEV in accordance with EN 12101‑2; and for daily natural ventilation
-
With BSY+ motor and synchronised electronics controlled via microprocessor
-
Option of up to 4 drives in one synchronous group
-
High‑speed function (HS) for especially fast opening windows in case of fire (SHEV)
-
Low running noises thanks to the innovative acoustic decoupling of the drive components
-
Special chain stabilisation and centred chain outlet
-
Compact design thanks to triple deflection of the chain
-
Use of a highly efficient, wear-free brushless motor
-
Relief of pressure on window gasket after closing process
-
Programmable drive functions and different drive parameters
-
Time-controlled reversing when an obstacle is detected in the CLOSED direction (active closing edge protection)
-
Integrated ACB (Advanced Communication Bus) bus interface with Modbus RTU protocol
-
The drive is integrated directly via open bus communication through the ACB (Advanced Communication Bus), e.g. in a building management system
Approvals / Certificates
Designs and technical data
CDM-1-ACB | CDM-1-ACB | CDM-1000-0600-1-ACB M1 | CDM-1000-0600-1-ACB M2 | CDM-1000-0600-1-ACB S1 | CDM-1000-0800-1-ACB M1 | CDM-1000-0800-1-ACB M2 | CDM-1000-0800-1-ACB S1 | CDM-1000-1000-1-ACB M1 | CDM-1000-1000-1-ACB M2 | CDM-1000-1000-1-ACB S1 | |
---|---|---|---|---|---|---|---|---|---|---|---|
Supply | Configuration dependent | 24 V DC / ±15 % / 2 A | 24 V DC / ±15 % / 2 A | 24 V DC / ±15 % / 2 A | 24 V DC / ±15 % / 2.5 A | 24 V DC / ±15 % / 2.5 A | 24 V DC / ±15 % / 2.5 A | 24 V DC / ±15 % / 3 A | 24 V DC / ±15 % / 3 A | 24 V DC / ±15 % / 3 A | |
Duty cycle | Variable designs possible | 30 % (ON: 3 min. / OFF: 7 min.) | 30 % (ON: 3 min. / OFF: 7 min.) | 30 % (ON: 3 min. / OFF: 7 min.) | 30 % (ON: 3 min. / OFF: 7 min.) | 30 % (ON: 3 min. / OFF: 7 min.) | 30 % (ON: 3 min. / OFF: 7 min.) | 30 % (ON: 3 min. / OFF: 7 min.) | 30 % (ON: 3 min. / OFF: 7 min.) | 30 % (ON: 3 min. / OFF: 7 min.) | 30 % (ON: 3 min. / OFF: 7 min.) |
Force of pressure | 1000 N | 1000 N | 1000 N | 1000 N | 1000 N | 1000 N | 1000 N | 1000 N | 1000 N | 1000 N | |
Tensile force | 1000 N | 1000 N | 1000 N | 1000 N | 1000 N | 1000 N | 1000 N | 1000 N | 1000 N | 1000 N | |
Nominal locking force | 3500 N | 3500 N | 3500 N | 3500 N | 3500 N | 3500 N | 3500 N | 3500 N | 3500 N | 3500 N | |
Service life | > 20000 double strokes | > 20000 double strokes | > 20000 double strokes | > 20000 double strokes | > 20000 double strokes | > 20000 double strokes | > 20000 double strokes | > 20000 double strokes | > 20000 double strokes | > 20000 double strokes | |
Stroke | - | 600 mm | 600 mm | 600 mm | 800 mm | 800 mm | 800 mm | 1000 mm | 1000 mm | 1000 mm | |
OPEN running speed | 7 mm/s | 7 mm/s | 7 mm/s | 7 mm/s | 7 mm/s | 7 mm/s | 7 mm/s | 7 mm/s | 7 mm/s | 7 mm/s | |
OPEN running speed - SHEV | Configuration dependent | 11.5 mm/s | 11.5 mm/s | 11.5 mm/s | 15 mm/s | 15 mm/s | 15 mm/s | 22.5 mm/s | 22.5 mm/s | 22.5 mm/s | |
CLOSED running speed | 5 mm/s | 5 mm/s | 5 mm/s | 5 mm/s | 5 mm/s | 5 mm/s | 5 mm/s | 5 mm/s | 5 mm/s | 5 mm/s | |
Show more information
|
|||||||||||
Request & Compare |
CDM-1-ACB |
CDM-1-ACB
|
CDM-1000-0600-1-ACB M1
|
CDM-1000-0600-1-ACB M2
|
CDM-1000-0600-1-ACB S1
|
CDM-1000-0800-1-ACB M1
|
CDM-1000-0800-1-ACB M2
|
CDM-1000-0800-1-ACB S1
|
CDM-1000-1000-1-ACB M1
|
CDM-1000-1000-1-ACB M2
|
CDM-1000-1000-1-ACB S1
|
Configure now |
The matching bracket for CDM-1-ACB
Please note: To install the drives, you will need 1x frame bracket and 1x sash bracket. Additional washers and fastening materials may be required for these brackets. Please contact your D+H partner for this.